By Razvan Toma · Founder & CEO, Ampervia · Last checked 2026-10-12 · Sources linked below
Recent European deals imply roughly 550 to 770 m² of land per MW for multi-storey data centers: about 22,000 m² for 40 MW in Madrid, 17,650 m² for 25 MW near Madrid, and 23,000 m² for about 30 MW near Milan. Single-storey or campus layouts need more. Sources (3)DCDDCD — Edgnex 40 MW data center in Madrid↗
ActivumSGActivumSG — €11m powered land sale to Pure DC↗
DCDDCD — Magnora acquires land outside Milan for data center development↗
Key facts
- Vicálvaro, Madrid: about 22,000 m² for 40 MW → ≈550 m² per MW (DCD).
- Meco, Madrid: 17,650 m² for 25 MW → ≈706 m² per MW (ActivumSG).
- Milan area (Magnora): 23,000 m² for about 30 MW → ≈767 m² per MW (DCD).
- Ratios are Ampervia’s division of the published figures.
| Site | Land | Power | m² per MW |
|---|---|---|---|
| Vicálvaro, Madrid | ≈22,000 m² | 40 MW | ≈550 |
| Meco, Madrid | 17,650 m² | 25 MW | ≈706 |
| Milan area | 23,000 m² | ≈30 MW | ≈767 |
What else the land must hold
- Substation or switchgear compound and transformer bays.
- Backup generators and fuel.
- Cooling plant, setbacks and access roads.
- Room for a second phase.
A quick sizing rule
For a 10 MW site, the published deals point to roughly 0.55–0.8 hectares; for 20 MW, about 1.1–1.5 hectares. Planning limits on height and coverage can push this up.
Questions
Does a 1-hectare plot fit a data center?
Sources
- DCD — Edgnex 40 MW data center in Madrid
- ActivumSG — €11m powered land sale to Pure DC
- DCD — Magnora acquires land outside Milan for data center development
Terms on this page: Powered land · IT load